Operation method:

1, ground resistance measurement

According to the ground electrode E (C2, P2) to be tested and the potential probe P1 and current probe C1, they are separated from each other by 20 meters in a straight line, so that the potential probe is in the middle position between E and C, and the probe is inserted into the earth as required.
Use a special wire to connect the ground resistance instrument terminals E (C2, P2), P1, and C1 to the position of the probe.
Turn on the ground resistance meter power switch "ON", select the appropriate gear lightly press the button indicator lights, the value of the meter LCD display is measured ground resistance.

2. Soil resistivity measurement

During the measurement, insert four probes along the straight line in the soil to be measured, and make the spacing between the probes equal. The distance between each distance is L. The depth of the probe is required to be L/20cm, and the distance from the probe is C1, P1 respectively. Each terminal of P2 and C2 is connected with four probes. If the resistance meter measures resistance R, the soil resistivity is calculated as follows:
Ф = 2πRL Ф - soil resistivity (Ωm), L-distance between probe and probe (m), R-resistance reading (Ω)
The soil resistivity measured by this method can be approximated as the average soil resistivity embedded in the area between the probes.
The probes used to measure the earth resistance and soil resistivity are generally aluminum alloy pipes or round steel with a diameter of 25 mm and a length of 0.5 to 1 m.
Maintenance and precautions:

1. When storing and keeping this watch, should pay attention to the ambient temperature and humidity, should be placed in a dry and ventilated place is appropriate, to avoid moisture, should prevent acid and alkali and corrosive gases.
2. When measuring the protective grounding resistance, be sure to disconnect the electrical equipment from the power supply. When measuring the grounding resistance less than 1Ω, they should be connected to the grounding body with dedicated wires respectively. C2 is on the inside of the outside P2 as shown in the figure.

3. When measuring the grounding resistance of a large grounding grid, it cannot be measured by the general wiring method. The buried plugging point can be selected according to the provisions in the ammeter and voltmeter measurement methods.
4, measuring the ground resistance is best repeated in different directions measured 3 to 4 times, take the average.
5, the instrument with rechargeable battery pack. When the rechargeable battery voltage in the unit is lower than 7.2V, the undervoltage symbol “←” is displayed in the upper left corner of the meter. Promptly charge the battery pack in time for about 8 to 14 hours. When the meter is not used for a long time, it should be charged and maintained regularly.

AGV Solution For Mobile Racking

AGV Solution For Mobile Racking, in simple terms, are movable shelving that can greatly improve space utilization, and a set of shelves only requires one channel to fix the tray shelves, serving only the two rows of shelves on both sides of the channel. So, within the same space, its storage capacity and efficiency are much higher than ordinary shelves. Mobile racking can actually be divided into light to medium mobile racking and heavy mobile shelving. They are as follows: What are light and medium-sized mobile shelving? Light and medium-sized mobile racking, also known as dense shelves, have evolved from light and medium-sized laminated shelves, requiring only a passage of about 1M. It can be said that light and medium-sized mobile shelves have the highest space utilization rate, and can also be divided into two types of mobile racking: manual and electric. Furthermore, the contact surfaces between each column of the light and medium-sized mobile shelving is equipped with cushioning, and the magnetic sealing strip is also equipped with a dustproof plate at the top and a rat proof device at the bottom. Each column is also equipped with a safety limit braking device and an anti tipping device, and a lock is arranged on the side for overall locking. The transmission mechanism is processed through precision machining and uses precision bearings, making the transmission flexible and stable. The spacing between layers can be freely adjusted according to needs. What is a heavy-duty mobile shelf? Heavy mobile shelves are generally evolved from heavy pallet shelves, which belong to an exposed structure, and each two rows of shelves are placed on the base. There are also walking wheels on the base, which can run along the track. In its chassis, there are also motors and reducers, alarm, and sensing devices installed. The storage system for heavy-duty mobile shelves only requires 1-2 channels, which has extremely high space utilization. Here, Hagrid also points out that heavy-duty mobile shelves must be electric, and goods are accessed by forklifts with zero support. The channel is usually about 3m, which can improve the utilization rate of the ground by about 80% compared to ordinary shelves.

Mobile shelving allow warehouses to save more floor space, with a floor usage rate range of 80%; Mobile shelves allow warehouses to save more floor space, with a floor usage rate range of 80%; Suitable for storage with few samples and multiple low-frequency frequencies; Relatively speaking, the storage capacity per unit area of mobile shelves can be increased to about twice that of pallet shelves; The use of mobile shelves allows direct access to every item of goods, without being subject to first in, first out restrictions, etc.

AGV Solution For Mobile Racking,Shelving System,Rolling Shelving Units,Mobile Rack

Suzhou Aomeijia Metalic Products Co,Ltd. , https://www.amjshelf.com